Sensors
Relative Humidity & Temperature Probes
Models 41382 & 41342
Model 41342 Temperature Probe offers accurate temperature-only measurement. Three output options are available: 0-1 VDC, 4-20 mA, and 4 wire RTD. Probes are easily installed in YOUNG naturally ventilated (multi-plate) and aspirated radiation shields. A junction box is provided for cable terminations.
Specifications
| Power Required: | 41382 | 41342 |
| V Option: 10-28 VDC | 8 mA | 5 mA |
| L Option: 10-28 VDC | 40 mA | 20 mA |
RELATIVE HUMIDITY: (41382)
Measuring Range: 0-100 %RH
Accuracy at 20 °C: ±2 %RH,
Stability: Better than ±1 %RH per year
Response Time: 10 seconds (without filter)
Sensor Type: Rotronic Hygromer™
Output Signal: V option: 0-1 VDC, L option: 4-20 mA
TEMPERATURE: (41382, 41342)
Calibrated Measuring Range: -50 to 50 °C (suffix C) -50 to 150 °F (suffix F)
Response Time: 10 seconds (without filter)
Accuracy at 0 °C: ±0.3 °C /optional ±0.1 °C NIST traceable calibration - 41342 only
Sensor Type: Platinum RTD
Output Signal: V Option: 0-1 VDC, L Option: 4-20 mA, 4 wire RTD (41342 only)
Recommended Radiation Shields:
Model 41003P Multi-Plate Radiation Shield
Model
43502 Aspirated Radiation Shield
| CABLE for 41342, 41342VC, 41342VF / 5 conductor shielded | 18446 | $0.50/ft. |
| CABLE for 41342LC, 41342LF / 2 conductor shielded | 18641 | $0.40/ft. |
| CABLE for 41382LC, 41382LF / 2 pair shielded | 18723 | $0.60/ft. |
| CABLE for 41382VC, 41382VF / 5 conductor shielded | 18446 | $0.50/ft. |
Complies with applicable CE directives. Specifications subject to change without notice.